ZN63-12(VS1-12)indoor high voltage vacuum circuit breaker for switchgear
High-voltage vacuum circuit breaker is named after its interrupting medium and the insulation medium of the contact gap after interrupting is high vacuum; vacuum circuit breaker has the advantages of small size, light weight, suitable for frequent operation and interrupting without maintenance, and is more popularly used in the distribution network.
VS1-12 indoor high voltage vacuum circuit breaker applies to power system of rated voltage 12kv as a protective and control unit for power grid equipment and industrial power equipment. It can equip with KYN28(GZS1), XGN, GG-1A and other types of switchgear panels. Related products: isolated handcart, fuse handcart and voltage transformer handcart.
Working principle
The components of the vacuum circuit breaker are vacuum interrupters, electromagnetic or spring operating mechanisms, brackets and other components. The conductive circuit is divided into the form of insulating cylinder and the form of solid-sealed pole.
The working principle of the vacuum circuit breaker is: when the moving and static contacts are opened under the action of the operating mechanism, an arc is generated between the contacts, and the surface of the contact volatilizes at high temperature. When passing through, a magnetic field is generated, and the arc moves rapidly along the tangential direction of the contact surface under the action of this magnetic field, and part of the metal vapor is condensed on the metal cylinder (shield), and the arc is extinguished when it naturally crosses zero. The strength of the medium quickly recovered.
Main Technical Parameters
Number |
Parameter |
Unit |
Value |
1 |
Rated voltage |
kV |
12 |
2 |
Rated frequency |
Hz |
50 |
3 |
Rated insulation level |
Rated short-time power frequency withstand voltage (1min)
(interphase, relative ground, fracture) |
Hz |
42 |
Rated lightning impulse withstand voltage
(phase, phase, port) |
kV |
75 |
4 |
Rated current |
A |
630 |
630 |
1250 |
1600 |
5 |
Rated short-circuit breaking current |
kA |
20 、25 、31.5 、40 |
6 |
Rated short-time withstand current (rated short-time thermal stability current) |
kA |
20 、25 、31.5 、40 |
7 |
Rated short-circuit making current |
kA |
50、 63、 80 、100 |
8 |
Rated peak withstand current (rated dynamic stable current) |
|
50、 63、 80 、100
|
9 |
Rated short-circuit duration (rated thermal stabilization time) |
S |
4 |
10 |
Rated short-circuit current breaking times |
|
O-0.3s-CO–180s-CO |
O-180s-CO-180s-CO(40kA) |
11 |
Mechanical life |
time |
30、20( 40kA) |
12 |
Rated single capacitor bank breaking current |
time |
20000 |
13 |
Rated single capacitor bank breaking current |
A |
630 |
14 |
Rated back-to-back capacitor bank breaking current |
A |
400 |
15 |
Out-of-phase earth fault breaking current |
A |
27.4 |
16 |
The moving and static contacts allow the accumulated thickness of wear |
mm |
3 |